Solar PV String & Array Sizing Calculator
Enter panel and inverter specifications to get the safe series string length with a temperature-corrected cold-day Voc check, MPPT window compliance, and total array kWp. Nothing uploaded.
Panel Specifications
Inverter specs
Inverter Specifications
Design conditions
Design Conditions
String Sizing Results
Always verify the final design with a qualified electrician or solar designer. Cold-day Voc must never exceed the inverter maximum input voltage.
Learn more: solar string sizing and cold-weather voltage
Why cold raises panel voltage
A panel's voltage rises as it gets colder. The tool corrects open-circuit voltage (Voc) with Voc x (1 + coefficient/100 x (low temperature - 25)). A 37.0 V panel with a coefficient of -0.28%/C at -20 C is 37.0 x (1 + 0.0028 x 45) = 41.7 V. A string sized on the 25 C rating can pass the inverter's maximum input voltage on a cold, clear morning.
Green Tech Renewables' string design article describes the same cold-voltage formula and says to take the lowest temperature from ASHRAE data for your location. It frames the design as two checks: a cold check that string voltage stays under the inverter's maximum DC input using Voc at record low temperatures, and a hot check that it stays above the start-up voltage using Vmp at peak cell temperature.
The longest string
The tool caps the string two ways: the inverter's maximum input voltage divided by the cold Voc, and the MPPT maximum voltage divided by the 25 C Voc. For the Growatt preset (600 V maximum, 550 V MPPT maximum) and the 37 V panel at -20 C, the first gives floor(600 / 41.7) = 14 panels and the second floor(550 / 37.0) = 14. The lower value is the longest string. At 14 panels the cold string is 583 V, under 600.
The shortest string
Heat lowers voltage, so the minimum is set on a hot day. The tool assumes a 70 C cell, applies the temperature coefficient to the panel's Vmp, and divides the MPPT minimum by that. For the 31 V Vmp panel the hot Vmp is 27.1 V. Against the Growatt's 80 V minimum that is 3 panels, and against the SMA preset's 125 V it is 5. The tool uses one coefficient for both Voc and Vmp, so enter your datasheet figure and check the Vmp coefficient too.
The tool does not add a safety margin beyond the cold voltage, and its 70 C cell temperature is an assumption. Check the result against your inverter's manual and the electrical rules where you live.
FAQ
Why is cold the risk for the long string?
Voltage climbs as cells cool, so the cold check is the one that can push a string over the inverter's maximum input. Heat lowers voltage, which matters for the minimum string instead.
What temperature should I use?
Use the lowest temperature your site is likely to see, such as the ASHRAE value the Green Tech article names, and not an average winter morning.
What if the string is too long or too short?
A string that exceeds the inverter's maximum input voltage can trip a fault or damage the input. A string that is too short may not stay above the MPPT minimum on a hot day, so it fails to track well.